Function
|
Measurement of 2/3/4-pole earth resistance, soil resistivity, earth voltage, AC voltage
|
Power Supply
|
DC 9V(Zi-Mn dry battery R14S 1.5V 6 PCS, continuous standby for 300 hours )
|
Measurement Range
|
Earth Resistance: 0.00Ω-30.00kΩ
|
Soil Resistivity: 0.00Ωm-9000kΩm
|
Measuring Mode
|
Precise 4-pole measurement, 3-pole measurement, simple 2-pole measurement
|
Measuring Method
|
Earth Resistance: rated current change-pole method, measurement current 20mA Max
Soil Resistivity: 4-pole measurement (Wenner method)
Earth Voltage: average rectification(between P(S)-ES)
|
Test Frequency
|
128Hz/111Hz/105Hz/94Hz(AFC)
|
Short-circuit Test Current
|
AC 20mA max
|
Open-circuit Test Current
|
AC 40V max
|
Test Voltage Wave
|
Sine wave
|
Electrode Distance Range
|
Can be set 1m-100m
|
Shift
|
Earth Resistance: 0.00Ω-30.00kΩ, automatic shift
|
Soil Resistivity: 0.00Ωm-9000kΩm, automatic shift
|
Backlight
|
Blue screen backlight, suitable for dim places
|
Display Mode
|
4-digital super-large LCD display, blue screen backlight
|
Measuring Indicator
|
During measurement, LED flash indicator, LCD count down display, progress bar indicator
|
LCD Frame Dimension
|
128mm×75mm
|
LCD Window Dimension
|
124mm×67mm
|
Dimension
|
L×W×H: 215mm×190mm×95mm
|
Standard Test Wire
|
4 wires: each for red 20m, black 20m, yellow 10m, and green 10m
|
Simple Test Wire
|
2 wires: each for red 1.6m and black 1.6m
|
Auxiliary Earthing Rod
|
4 rods: Φ10mm×150mm
|
Measuring Rate
|
Earth voltage: about 3 times/second
|
Earth resistance, soil resistivity: about 5 seconds/time
|
Measuring Times
|
Over 5000 times (Short-circuit test, interval time should be at least 30 seconds)
|
Line Voltage
|
below AC 600V
|
RS232 Interface
|
Possess RS232 interface, software supervision, storage data can be uploaded to computer, saved or printed.
|
Communication Wire
|
One piece of RS232 communication wire, with length 1.5m
|
Data Storage
|
300 sets, “MEM” icon storage indicator, flash display “FULL” icon to indicate storage is full
|
Data Hold
|
Data hold function: “HOLD” icon display
|
Data Access
|
Data read function: “READ”icon display
|
Overflow Display
|
Exceeding measuring range overflow function: “OL” icon display
|
Interference Test
|
Recognize interference signal automatically, “NOISE” icon display when interference voltage exceed 5V
|
Auxiliary Earthing Test
|
Can measure auxiliary earth resistance, 0.00KΩ-30kΩ(100R+rC<50kΩ, 100R+rP<50kΩ)
|
Alarm Function
|
When measuring value exceeds alarm setting value, there is “Toot-toot-toot” alarm hint
|
Battery Voltage
|
When battery voltage decreases to about 7.5V, battery voltage low icon will display, reminding to replace battery.
|
Power Consumption
|
Standby: about 20mA (Backlight shut off)
|
Boot and with backlight: about 45mA (25mA without backlight)
|
Measurement: about 100mA (Backlight shut off)
|
Weight
|
Total weight: 4.5kg (including package)
|
Tester: 1443g (including battery)
|
Tesing wires: 1560g
|
Auxiliary earthing rods: 935g (4pcs)
|
WorkingTemperature & Humidity
|
-10℃-40℃, below 80%rh
|
Storage temperature & humidity
|
-20℃-60℃, below 70%rh
|
Overload Protection
|
Measuring earth resistance: between each interfaces of C(H)-E、P(S)-ES,AC 280V/3 seconds
|
Insulation Resistance
|
Over 20MΩ (between circuit and enclosure it is 500V)
|
Withstanding Voltage
|
AC 3700V/rms (Between circuit and enclosure)
|
Electromagnetic Features
|
IEC61326(EMC)
|
Protection Type
|
IEC61010-1 (CAT Ⅲ 300V、CAT IV 150V、Pollution 2), IEC61010-031, IEC61557-1 (Earth resistance), IEC61557-5 (Soil resistivity), JJG 366-2004
|